# Hoshizaki ice machine beeping? What 1, 2, 3, 6 and 7 beeps mean (error codes)

Last updated 2026-11-22

**Short answer:** Hoshizaki crescent cube machines with the "J" control board report faults by beeping every 3 seconds, and each alarm shuts the icemaker down. 1 beep means the evaporator went above 127 °F; 2 beeps mean the harvest took more than 20 minutes two cycles in a row; 3 beeps mean the freeze cycle ran past the freeze timer (60 minutes as set at the factory) two cycles in a row. Reset these with the ALARM RESET button on the control board, with the power on. 6 and 7 beeps mean the board's control voltage fell to about 92 V AC or rose to about 147 V AC; they clear by themselves when the voltage is corrected. A single beep when you switch to ICE is normal.

**Safety:** Disconnect power before servicing, and follow the manufacturer's service manual. Refrigerant work is for a qualified refrigeration technician (EPA Section 608 certified; trained for flammable refrigerants on R-290 machines), electrical work for a qualified person. Safety disclaimer: https://icepartsdb.com/legal/safety-disclaimer

A Hoshizaki ice machine that beeps every 3 seconds has stopped on an alarm: count the beeps, then find them in the
table below. The "J" control board in the Hoshizaki crescent cubers these manuals cover (the KML-325, KML-500 and KML-700 MAJ / MWJ
/ MRJ and the KM-1100MAJ50, listed at the end) has no display. It reports a fault by beeping a set number of times,
every 3 seconds, and its LEDs show which step of the cycle the machine is in. The table below lists every beep code
those manuals give: 1, 2, 3, 6 and 7 beeps.

**Check your board first.** The model letters don't tell you the board: Hoshizaki's parts list No. 71416 (revised
1-14-2022, page 4) gives the KM-350, KM-520 and KM-660 MAJ / MWJ / MRJ a "K" control board (2A8242-02) or, from later
serial numbers, a "K+" board (2A9678-01), not the "J" board. Find your model's parts list or service manual (the model
and serial number are on the data plate): it names the board. For a machine with another board, or an older model
such as a KM-…MAH, use that model's service manual: its alarms may differ.

**One beep when you move the control switch to ICE is normal.** The 1-beep alarm repeats every 3 seconds.

## The alarm codes

Each of these safeties shuts the icemaker down.

| Beeps | Alarm | What triggers it | What Hoshizaki says to check |
| --- | --- | --- | --- |
| 1 | High evaporator temperature | The thermistor reads above 127 °F (53 °C) | A harvest problem (hot gas valve or its relay stuck on), hot water entering the icemaker, a stuck headmaster (C.P.R.) valve, or a shorted thermistor |
| 2 | Harvest backup timer | The harvest lasts more than 20 minutes, two cycles in a row | An open (failed) thermistor, a hot gas valve that doesn't open, an expansion valve or liquid line valve leaking by, a low refrigerant charge, an inefficient compressor; on water-cooled models also a water regulating valve leaking by |
| 3 | Freeze timer | The freeze cycle runs past the freeze timer setting (60 minutes as set at the factory), two cycles in a row | A float switch stuck closed (up), an inlet water valve or hot gas valve leaking by, a water pump not pumping, an expansion valve not feeding properly, a liquid line valve not opening, a low charge, a headmaster not bypassing, an inefficient compressor |
| 6 | Low voltage | The board's control voltage falls to 92 V AC (±5%) or below | Hoshizaki gives no checklist: the alarm clears by itself when the voltage is corrected. These machines are hard-wired, so have an electrician check the supply |
| 7 | High voltage | The control voltage rises to 147 V AC (±5%) or above | As for 6 beeps |

The parts behind these alarms: [Hoshizaki](https://icepartsdb.com/hoshizaki/thermistors-sensors) thermistors & sensors (the [thermistor](https://icepartsdb.com/glossary#thermistor) that times the [harvest](https://icepartsdb.com/glossary#harvest)),
[Hoshizaki](https://icepartsdb.com/hoshizaki/hot-gas-valves) hot gas valves, [Hoshizaki](https://icepartsdb.com/hoshizaki/float-switches) float switches, [Hoshizaki](https://icepartsdb.com/hoshizaki/water-inlet-valves) water inlet valves,
[Hoshizaki](https://icepartsdb.com/hoshizaki/water-pumps) water pumps and [Hoshizaki](https://icepartsdb.com/hoshizaki/control-boards) control boards. Refrigeration parts (expansion, liquid line and
[headmaster](https://icepartsdb.com/glossary#headmaster) valves, refrigerant charge, compressor) are work for a technician certified under EPA Section 608.

## How to reset a Hoshizaki alarm

- **1, 2 and 3 beeps:** press the ALARM RESET button on the control board while it is beeping, with the power on. After
  a reset the machine starts again with its 1-minute water fill. **Warning: risk of electric shock.** The board is live
  while you do this; don't touch any terminal. Hoshizaki intends these procedures for qualified service technicians.
- **6 and 7 beeps:** these reset by themselves once the control voltage is back in range. While the voltage protection is
  active, the red "POWER OK" LED on the board is off.

If the same alarm comes back, the cause is still there. The freeze timer exists to prevent freeze-ups; resetting again
and again without fixing the cause risks one.

## What the LEDs on the control board mean

- **Red "POWER OK":** the board is getting its control voltage. It is also off, **without any beep**, when the
  high-pressure switch has tripped, a fuse has blown or the control switch is off; check those before suspecting the
  board.
- **Green "BC CLOSED" / yellow "BC OPEN":** the [bin control](https://icepartsdb.com/glossary#bin-control). Yellow means the bin control is open: the bin is full,
  or the jumper on the board's bin control connector is missing or loose. The icemaker stays off while it is open. A
  thermostatic bin control also opens, and stops the machine, when the room is colder than about 45 °F (7 °C), even with
  an empty bin.
- **Four green relay LEDs:** which relays are on, and so which step of the cycle the machine is in. Counted from the outer
  edge of the board, they are in the order 1, 4, 3, 2.

| Step | Green LEDs on | What is running | How long |
| --- | --- | --- | --- |
| Water fill at start-up | 4 | Inlet water valve | 1 minute (repeated until the float switch shows water) |
| Harvest | 1, 4, 2 | Compressor, hot gas valve, inlet water valve | From about 1–2 minutes up to the 20-minute backup timer |
| Harvest assist (pump) | 1, 3, 2 | Compressor, hot gas valve, water pump | Up to 50 seconds |
| Freeze | 1 | Compressor, fan, water pump, liquid line valve | From 5 minutes up to the freeze timer |
| Anti-slush (if enabled) | 1, 3 | Water pump off for 10 seconds when the thermistor reaches 36 °F | 10 seconds |
| Pump-out (drain) | 1, 3, 2 | Compressor, hot gas valve, water pump, drain valve | 10–20 seconds |

Knowing the step narrows a fault down: a machine that stays in the 1-minute fill (LED 4) is waiting for water, because
the [float switch](https://icepartsdb.com/glossary#float-switch) hasn't closed; one that cycles normally but makes little ice points to water flow or the refrigeration
side.

## Before you call a technician

Switch the machine off and turn off and lock out the power supply before opening it or cleaning anything inside.

1. **Clean the float switch** (drain the water tank first): scale makes it stick, and a float stuck up is the first item
   on Hoshizaki's 3-beep list. See the [float switch guide](https://icepartsdb.com/guides/ice-machine-float-switch).
2. **Check for an inlet water valve leaking through** during the freeze cycle (water trickling in when it shouldn't);
   see the [water inlet valve guide](https://icepartsdb.com/guides/ice-machine-water-inlet-valve).
3. **Clean the condenser** (air-cooled) and make sure the room isn't too hot.
4. **Clean and descale the machine**; see [how to clean a commercial ice machine](https://icepartsdb.com/guides/how-to-clean-commercial-ice-machine).
5. **Note the number of beeps and when it happens** (in harvest or in freeze) for the technician.

Hoshizaki lists low water pressure and clogged external water filters among the causes of long harvests and freeze-ups.
With no water at all, the machine stays in its fill cycle instead of alarming.

## Questions and answers

### Why is my Hoshizaki ice machine beeping 3 times?

Three beeps is the freeze timer alarm: the freeze cycle ran past the timer setting (60 minutes as set at the factory) two
cycles in a row, and the machine shut down. Hoshizaki's list starts with a float switch stuck up, then an inlet water
valve or hot gas valve leaking through, a water pump not pumping, and refrigeration problems. Clean the float switch
first and check that the inlet water valve isn't leaking through.

### What does 1 beep mean on a Hoshizaki ice machine?

If it repeats every 3 seconds, the evaporator thermistor read above 127 °F and the machine shut down. Hoshizaki says to
check for a harvest problem (hot gas valve or relay stuck on), hot water entering the icemaker, a stuck headmaster valve,
or a shorted thermistor. A single beep when you switch to ICE is normal.

### What do 2 beeps mean on a Hoshizaki?

The harvest took more than 20 minutes in two cycles in a row. Hoshizaki says to check for an open thermistor, a hot gas
valve that doesn't open, valves leaking by, a low charge or an inefficient compressor.

### How long is the harvest cycle on a Hoshizaki ice machine?

Usually a few minutes. The board ends the harvest once the thermistor on the evaporator outlet reaches 48 °F and its
harvest timer (60 to 180 seconds) has run out. The 20-minute harvest backup timer is the limit: a harvest that passes it
two cycles in a row sets off the 2-beep alarm.

### How do I reset a Hoshizaki ice machine?

Press the ALARM RESET button on the control board while it beeps, with the power on (risk of electric shock: don't touch
any terminal). The machine restarts with a 1-minute fill. The voltage alarms (6 and 7 beeps) reset by themselves when the
voltage is corrected. Other brands: [how to reset a commercial ice machine](https://icepartsdb.com/guides/how-to-reset-commercial-ice-machine).

### Why does my Hoshizaki keep beeping after I reset it?

The fault that caused the alarm is still there. Note the number of beeps, look at the checks in the table above, and fix
the cause before resetting again.

## Sources

- Hoshizaki America, *KML-325MAJ/MWJ, KML-500MAJ/MWJ, KML-700MAJ/MWJ/MRJ Modular Crescent Cuber Service Manual*,
  No. 73215, issued 6-16-2017 (U.S. models): "LED Lights and Audible Alarm Safeties" (page 34), control board check and
  alarm reset (page 22), bin control (pages 21–22, 28), freeze timer (page 38), sequence of operation (pages 13–19),
  harvest timer (page 35).
- Hoshizaki America, *KM-1100MAJ50 Modular Crescent Cuber Service Manual*, No. 73231, issued 9-12-2018: section III.B
  (page 29) and II.C (page 17). This is a 220–240 V export model; its alarm table matches the U.S. KML manual above.
- Service manuals for every model are published by [Hoshizaki America](https://www.hoshizakiamerica.com). Settings can
  differ between control board versions, so the manual for your model is the authority.

## More guides

- [Ice machine not making ice? Causes, checks and the parts that fix them](https://icepartsdb.com/guides/ice-machine-not-making-ice)
- [Manitowoc ice machine error codes (Indigo NXT E01 to E31): meanings and fixes](https://icepartsdb.com/guides/manitowoc-ice-machine-error-codes)
- [Scotsman ice machine error codes: Prodigy code display meanings and fixes](https://icepartsdb.com/guides/scotsman-ice-machine-error-codes)
- [Ice-O-Matic ice machine error codes: CIM flashing lights, GEM and MFI service lights](https://icepartsdb.com/guides/ice-o-matic-ice-machine-error-codes)
- [How to reset a commercial ice machine (Hoshizaki, Manitowoc, Scotsman, Ice-O-Matic)](https://icepartsdb.com/guides/how-to-reset-commercial-ice-machine)
- [Ice machine water inlet valve: symptoms, testing and replacement](https://icepartsdb.com/guides/ice-machine-water-inlet-valve)
- [Ice machine water pump: symptoms, testing and replacement](https://icepartsdb.com/guides/ice-machine-water-pump)
- [Ice machine float switch and water level probe: symptoms, testing and replacement](https://icepartsdb.com/guides/ice-machine-float-switch)

## Data sources

- [How we build these pages (methodology)](https://icepartsdb.com/legal/editorial-policy)

Last updated: 2026-11-22

Canonical URL: https://icepartsdb.com/guides/hoshizaki-ice-machine-error-codes

Report a correction to this page: https://icepartsdb.com/contact/correction?page=%2Fguides%2Fhoshizaki-ice-machine-error-codes