# Ice machine refrigerants and the EPA rules: R-404A, R-410A, R-134a, R-290 and the 2026–2027 deadlines

Last updated 2026-11-22

**Short answer:** Under the EPA's Technology Transitions rule (40 CFR 84.54), self-contained ice machines made or imported from January 1, 2026 that make up to 1,000 lb a day (batch) or 1,200 lb (continuous) can't use an HFC refrigerant (or a blend containing one) with a GWP of 150 or more; larger ones can't use R-404A, R-410A, R-134a and other listed HFCs from January 1, 2027. From January 1, 2027 no remote-condenser system with R-404A or other listed HFCs may be installed, even from used components. EPA's May 2026 rule (91 FR 31284) changed none of this. Existing and used machines can keep running, be repaired and be sold used; from 2029 refrigerant added to HFC ice machines must be reclaimed.

**Safety:** Disconnect power before servicing, and follow the manufacturer's service manual. Refrigerant work is for a qualified refrigeration technician (EPA Section 608 certified; trained for flammable refrigerants on R-290 machines), electrical work for a qualified person. Safety disclaimer: https://icepartsdb.com/legal/safety-disclaimer

The refrigerant in an ice machine decides which parts fit it, who may service it, and, now, whether it can be made or
installed new. This guide explains the refrigerants in Hoshizaki, Manitowoc and Scotsman machines and the U.S. rules
that apply to them, from the regulations themselves. It was checked against the Code of Federal Regulations as current
on November 19, 2026. It is a summary, not legal advice: the regulation text is the authority.

## Which refrigerant does my ice machine use?

- **The data plate** names the refrigerant and the charge. Hoshizaki's rating label and nameplate give the refrigerant
  data; Manitowoc's model/serial tag lists the charge; Scotsman's service manuals refer to the nameplate charge.
- **Current Manitowoc model numbers** (Indigo NXT and later) show it in the third letter: P is R-290 (propane), F
  R-404A, T R-410A, B R-600a, E R-134a and K R-452A (so an IYT0500A uses R-410A). Older Manitowoc models don't, so read
  the plate. See [how to read a model number](https://icepartsdb.com/guides/find-ice-machine-model-number-and-part-number).
- **The machine pages** here show the refrigerant where the ENERGY STAR data lists it: [Hoshizaki](https://icepartsdb.com/hoshizaki/machines), [Manitowoc](https://icepartsdb.com/manitowoc/machines) and [Scotsman](https://icepartsdb.com/scotsman/machines) ice machines.

## The refrigerants in commercial ice machines

| Refrigerant | Type | GWP (EPA) | Where you find it |
| --- | --- | --- | --- |
| R-22 | HCFC (ozone-depleting) | — | Old machines. No production or import in the U.S. since January 1, 2020. |
| R-404A | HFC blend | about 3,920 | EPA: the usual refrigerant in remote-condenser machines, and common in self-contained ones |
| R-410A | HFC blend | about 2,090 | EPA: common in self-contained machines; Manitowoc's Indigo NXT "T" models |
| R-134a | HFC | 1,430 | Some self-contained machines and heads (ENERGY STAR lists both); makers say it works well depending on size |
| R-448A, R-449A | HFC/HFO blends | about 1,390–1,400 | EPA lists them as available substitutes for remote-condenser machines |
| R-513A, R-450A | HFC/HFO blends | 630 and 601 | EPA lists them as substitutes for large self-contained machines |
| R-290 (propane) | Hydrocarbon | 3.3 | Most self-contained models now on the ENERGY STAR list; flammable |

GWP (global warming potential) compares a gas's warming effect with carbon dioxide. The figures are the EPA's, from the
Technology Transitions rule and its GWP table; for blends the GWP is the weighted sum of the parts. The manufacturers'
trade association, in its 2025 petition to the EPA, said R-404A and R-134a have historically worked well for ice
machines depending on size, because their low temperature glide lets ice freeze evenly and harvest properly.

## The EPA rule for new ice machines

The American Innovation and Manufacturing (AIM) Act of 2020 lets the EPA restrict high-GWP HFCs sector by sector. The
EPA's Technology Transitions rule, published October 24, 2023 (88 FR 73098) and codified at 40 CFR 84.54, sets these
limits for automatic commercial ice machines:

| Ice machine | Restriction | From |
| --- | --- | --- |
| Self-contained, batch type (cubers), harvest rate up to 1,000 lb per 24 h | No manufacture or import with an HFC, or a blend containing one, with a GWP of 150 or more | January 1, 2026 |
| Self-contained, continuous type (flake, nugget), harvest rate up to 1,200 lb per 24 h | No manufacture or import with an HFC, or a blend containing one, with a GWP of 150 or more | January 1, 2026 |
| Self-contained, batch over 1,000 lb or continuous over 1,200 lb | No manufacture or import with listed HFCs, including R-404A, R-407A, R-407C, R-407F, R-410A, R-507A and HFC-134a (R-134a) | January 1, 2027 |
| Remote condenser | No installation of a new system with listed HFCs, including R-404A, R-407B, R-410B and R-507A (R-410A, R-134a, R-448A and R-449A are not on this list) | January 1, 2027 |

What the terms mean:

- **Self-contained** is EPA's term for a machine whose refrigeration system is complete and sealed in the factory: the
  evaporator and condenser are in the cabinet, with no external refrigerant connections, and the storage compartment is
  integral "if provided". That includes air- and water-cooled ice-making heads that sit on a separate bin, not only
  machines with a built-in bin: the EPA's HFC FAQ calls an ice machine that is functional when it leaves the factory a
  product.
- **Remote condenser** machines have the condenser elsewhere, connected by refrigerant lines charged in the field, so
  the EPA treats them as systems and restricts their installation. "Install" means completing a field-assembled
  system's circuit, including charging it to full charge (40 CFR 84.52), and assembling a system for the first time from
  used or new components counts as an installation (40 CFR 84.54(e)(1)). The EPA's FAQ says no new system may be
  installed with a restricted HFC after the compliance date, even if its components were made before that date, used or
  held in inventory.
- **Harvest rate** is determined with the DOE test procedure (10 CFR 431.134): the certified figure at 90 °F air and
  70 °F water, not a brochure figure at 70 °F air and 50 °F water.
- **Sell-through:** a new product made or imported before its date can still be sold for three more years (40 CFR
  84.54(b)). After that (January 1, 2029 for the smaller self-contained machines and January 1, 2030 for the larger
  ones) new restricted units can no longer be sold, distributed or exported. An unused machine counts as new: the
  used-product exemption needs "ordinary operation or utilization by a consumer" and doesn't cover new equipment bought,
  held and resold (88 FR 73098, used equipment). There is no sell-through for remote systems: the 2027 date is an
  installation date.
- **Labels:** from the same dates, new ice machines that use any HFC must carry a permanent label with the refrigerant,
  the year of manufacture, and the harvest rate relative to the threshold with the type (batch or continuous). New
  components for remote systems (such as compressors, condensers and evaporators) made for a restricted HFC must be
  labeled "For servicing existing equipment only".

## What EPA's May 2026 reconsideration rule changed for ice machines

Nothing. The EPA's final rule "Phasedown of Hydrofluorocarbons: Reconsideration of Certain Regulatory Requirements
Promulgated Under the Technology Transitions Provisions of the American Innovation and Manufacturing Act of 2020" was
published on May 26, 2026 (91 FR 31284) and took effect on July 27, 2026. It changed requirements for:

- refrigerated transport (intermodal containers);
- industrial process refrigeration, including chillers used in semiconductor manufacturing;
- retail food supermarket systems and retail food remote condensing units;
- cold storage warehouses;
- refrigerated laboratory centrifuges and shakers;
- condensing units in residential and light commercial air conditioning and heat pumps, including letting inventory
  made or imported before January 1, 2025 still be installed.

Automatic commercial ice machines are not among them. The text of 40 CFR 84.54(a)(8) (self-contained ice machines) and
84.54(c)(14) (remote-condenser ice machines) is word for word the same before and after the rule. The preamble mentions
ice machines only to say that an ice machine in a supermarket is not part of the supermarket system subsector, and in
listing the equipment a safety standard covers. Its only change to the labeling section corrects a cross-reference.

Ice machine makers have asked for more time. On December 1, 2025, the North American Association of Food Equipment
Manufacturers (NAFEM), with Follett and Hoshizaki America, petitioned the EPA to move both ice machine dates by three
years, to January 1, 2029 and January 1, 2030. The EPA lists it as a petition for reconsideration that is under review
(its petitions page, updated August 13, 2026). As of November 19, 2026 the regulation still shows January 1, 2026 and
January 1, 2027, and the EPA's table of HFC restrictions by sector lists the same dates.

## Existing machines, repairs and used machines

- **Existing machines can keep running.** The rule doesn't restrict the continued use of existing products. The EPA
  says a product may be serviced and repaired throughout its useful life, including replacing components, and that
  components to repair existing equipment may still be made, imported and sold.
- **Used machines can be sold.** The ban on selling restricted products doesn't apply to products after a period of
  ordinary use (40 CFR 84.56(c)). The EPA says the exemption covers individuals selling equipment they used and
  businesses that deal in used goods, but not new equipment bought, held and resold. Its FAQ adds that owners may sell
  or move used products. That is about self-contained machines (products); for remote systems see the next point.
- **Installing a used remote R-404A machine is a different question.** From January 1, 2027 no one may install a
  remote-condenser ice machine system that uses R-404A or the other listed HFCs (40 CFR 84.54(c)(14)), and the EPA says
  such a system can't be built from used or stocked components after that date. The EPA hasn't said that moving a whole
  used system to a new site is exempt, so assume you can't install one from 2027, and ask your refrigeration contractor
  before you buy. R-410A remote machines are not on the list.
- **Importing a used machine is different.** The used-product exemption doesn't extend to importing (except for
  personal use, conveyances and recycling), so buy a used self-contained machine with a restricted refrigerant from a
  U.S. seller. See [buying a used ice machine on eBay](https://icepartsdb.com/guides/buying-used-ice-machine-ebay).
- **Equipment that existed in the U.S. before December 27, 2020** is outside the rule.
- **No conversions to R-290.** The EPA lists R-290 for new self-contained ice machines designed for it, and its listing
  says it may not be used "as a conversion or 'retrofit' refrigerant for existing equipment designed for other
  refrigerants" (89 FR 50410, appendix V). Don't change an ice machine's refrigerant without the maker's approval.

## Servicing rules: certification, reclaimed refrigerant and leaks

- **Technician certification.** Anyone who opens the refrigerant circuit of a machine that uses R-22, an HFC or an
  HFC/HFO blend must be certified under Section 608 (40 CFR 82.161): Type I for small appliances, which the EPA defines
  as factory-sealed units with 5 lb or less of refrigerant and which include under-the-counter ice makers (40 CFR
  82.152); Type II for other medium-, high- and very high-pressure appliances, including remote systems. Venting these
  refrigerants is prohibited (40 CFR 82.154(a)).
- **Propane in self-contained machines is exempt from Section 608, not from everything.** 40 CFR 82.154(a)(1)(viii)
  exempts R-290 in self-contained commercial ice machines from the venting prohibition and the rest of the Section 608
  rules, so federal certification isn't required for them. That doesn't mean propane may always be vented: the EPA says
  propane recovered or disposed of from ice machines is likely hazardous waste under RCRA, and its listing says only
  technicians trained in flammable refrigerants should service them (89 FR 50410, appendix V; the machine's label reads
  "To Be Repaired Only By Trained Service Personnel"). State and local codes and the maker's service rules still apply.
  The exemption is for propane only: isobutane (R-600a), used in a few undercounter units, is not exempt in ice
  machines (40 CFR 82.154(a)(1)(ix)).
- **Reclaimed refrigerant from 2029.** From January 1, 2029, refrigerant used to service or repair a commercial ice
  machine (self-contained or remote) that contains an HFC must be reclaimed refrigerant with no more than 15 percent
  virgin HFC by weight (40 CFR 84.112(e), from the EPA's 2024 rule, 89 FR 82682). The EPA says refrigerant recovered
  from a machine may still be recycled back into it or into another machine of the same owner. Two grocery trade groups
  (FMI and NGA) have asked the EPA to delete this requirement; the EPA lists their petitions as under review.
- **Leak repair.** Since January 1, 2026, appliances with a full charge of 15 lb or more of refrigerant containing an
  HFC must have leaks repaired when they exceed set leak rates (40 CFR 84.106). Most ice machines hold far less:
  Manitowoc's handbook lists its self-contained Indigo NXT machines at under 3 lb and its remote systems at up to
  14.75 lb including the line set. Some large remote systems are over the line: Hoshizaki lists 15 lb 14 oz of R-404A
  for its F-2001MRJ flaker with the URC-22F condenser, so the leak repair rules apply to it. Check the plate.
- **Less HFC to go round.** U.S. HFC production and consumption are capped at 60 percent of the baseline for 2024–2028,
  30 percent for 2029–2033, 20 percent for 2034–2035 and 15 percent from 2036 (40 CFR 84.7).

## R-290 (propane) ice machines: what's different

- **Flammable, in small amounts.** R-290 is in ASHRAE safety group A3 (low toxicity, higher flammability). The EPA
  notes it can burn if its concentration exceeds 2.1 percent by volume in the presence of an ignition source.
  Charges are small: Manitowoc lists 5.3 oz (150 g) for its air-cooled IP0500 and 8.8 oz (250 g) for the water-cooled
  one.
- **Safety standard and markings.** The EPA first listed R-290 for new self-contained commercial ice machines in 2016
  (81 FR 86778) and updated the conditions in 2024 (89 FR 50410): machines must be designed for the refrigerant, meet the
  UL 60335-2-89 safety standard (new models since September 30, 2024; unchanged older models could stay with UL 563),
  carry flammable-refrigerant warning labels and have red markings at service ports, pipes and hoses.
- **Where it can go.** Makers set limits: Manitowoc's handbook gives a minimum room size for each R-290 model and says
  they can't be installed in hallways, public corridors, public lobbies, evacuation routes or small spaces.
- **Parts are specific.** Compressors ([Hoshizaki](https://icepartsdb.com/hoshizaki/compressors), [Manitowoc](https://icepartsdb.com/manitowoc/compressors) and [Scotsman](https://icepartsdb.com/scotsman/compressors) compressors), valves and controls for an R-290 machine are made for it,
  and its electrical parts are chosen not to ignite a leak: the makers' petition says that with flammable refrigerants
  the components must be tested to be spark proof. Don't fit an electrical part that isn't listed for that model.
  Buy by the number on the old part or in the parts list for your exact model; see
  [how to find the right part number](https://icepartsdb.com/guides/find-ice-machine-model-number-and-part-number).

## What this means for you

- **You own an R-404A, R-410A or R-134a machine:** keep using it and repair it. Budget for refrigerant possibly costing
  more as the HFC supply shrinks (40 CFR 84.7), and have leaks fixed rather than topped up.
- **You are buying new:** a self-contained machine up to 1,000 lb a day (1,200 lb for flake or nugget) made or
  imported in 2026 or later can't use an HFC with a GWP of 150 or more; most use R-290. Units made before 2026 with
  R-404A, R-410A or R-134a may still be sold new until December 31, 2028 (larger machines: made before 2027, until
  December 31, 2029), and an unused open-box unit counts as new. Check the room size and location limits in its
  installation manual.
- **You are buying used:** a used self-contained HFC machine is legal to buy, move and run. Price in its future
  servicing; see [buying a used ice machine](https://icepartsdb.com/guides/buying-used-ice-machine-ebay).
- **You are installing a remote machine:** from January 1, 2027 a new installation can't use R-404A or the other listed
  HFCs, and the EPA's FAQ says used or stocked components can't be used to build such a system after the date. An
  installation counts when the system is charged to full charge (40 CFR 84.52), so a remote R-404A system would have to
  be charged by December 31, 2026. R-410A remote machines (Manitowoc's "T" models) are not restricted. If you plan to
  install a remote machine that uses a listed HFC, ask your refrigeration contractor how the rule applies before you
  buy.

## Questions and answers

### Are R-404A ice machines being banned?

Not existing ones. The EPA's rule stops new self-contained ice machines up to 1,000 lb a day (1,200 lb for flake and
nugget) with refrigerants of GWP 150 or more being made or imported from January 1, 2026, and stops R-404A in larger
self-contained machines and in new remote installations from January 1, 2027. Machines already in use can keep running,
be repaired, and be sold used.

### Can I still install a remote ice machine that uses R-404A?

Only if it is installed, meaning charged to full charge, by December 31, 2026. From January 1, 2027 the EPA's rule (40
CFR 84.54(c)(14)) prohibits installing a remote-condenser ice machine system that uses R-404A or the other listed HFCs,
and the EPA's FAQ says such a system can't be built from used or stocked components after the date. The EPA hasn't
said that moving a whole used system to a new site is exempt, so assume a used R-404A remote machine can't be installed
from 2027, and ask your refrigeration contractor before you buy. Remote machines with R-410A, R-134a, R-448A or R-449A
are not on the list.

### Can I still repair my R-404A ice machine?

Yes. The EPA says products may be serviced and repaired throughout their useful life, and replacement components can
still be made and sold. Refrigerant work must be done by an EPA Section 608 certified technician, and from January 1,
2029 refrigerant added during the repair must be reclaimed (refrigerant recovered from the same machine may go back
in).

### What did the EPA's May 2026 rule change for ice machines?

Nothing. The reconsideration rule published May 26, 2026 (91 FR 31284, effective July 27, 2026) changed requirements for
refrigerated transport, industrial process refrigeration, supermarket and retail remote condensing systems, cold
storage warehouses, laboratory equipment and residential air conditioning. The ice machine limits for 2026 and 2027
were left as they were.

### Is an R-290 ice machine safe?

R-290 is flammable, so the EPA allows it in new self-contained ice machines only under conditions: the machine must
meet the UL 60335-2-89 safety standard (designs unchanged since before September 30, 2024 may still follow UL 563), be
designed for R-290, and carry warning labels and red-marked service points.
Follow the maker's installation limits, such as Manitowoc's minimum room size and its ban on hallways and evacuation
routes, and have it serviced by a technician trained for flammable refrigerants.

### Can I convert my ice machine to R-290?

No. The EPA lists R-290 only for new self-contained ice machines designed for it, and its listing says R-290 may not be
used as a conversion or retrofit refrigerant for existing equipment designed for other refrigerants. An R-404A or
R-410A machine is not built for a flammable refrigerant.

### Do I need EPA certification to work on an ice machine?

To open the refrigerant circuit of a machine that uses R-22 or an HFC such as R-404A, R-410A or R-134a, yes: Section
608 Type I for factory-sealed units with 5 lb or less (including under-the-counter ice makers), Type II for machines
with more refrigerant or charged in the field, such as remote systems. Propane (R-290) in self-contained commercial ice
machines is exempt from Section 608, but the EPA says only technicians trained for flammable refrigerants should
service them, and recovered propane is likely hazardous waste. Changing a water pump, water valve or sensor doesn't
open the refrigerant circuit.

## Sources

- U.S. EPA, [*Phasedown of Hydrofluorocarbons: Reconsideration of Certain Regulatory Requirements Promulgated Under the Technology Transitions Provisions of the American Innovation and Manufacturing Act of 2020*](https://www.federalregister.gov/documents/2026/05/26/2026-10387/phasedown-of-hydrofluorocarbons-reconsideration-of-certain-regulatory-requirements-promulgated-under),
  final rule, 91 FR 31284, May 26, 2026, effective July 27, 2026 (summary, supermarket subsector note, regulatory text).
- U.S. EPA, [*Phasedown of Hydrofluorocarbons: Restrictions on the Use of Certain Hydrofluorocarbons Under the American Innovation and Manufacturing Act of 2020*](https://www.federalregister.gov/documents/2023/10/24/2023-22529/phasedown-of-hydrofluorocarbons-restrictions-on-the-use-of-certain-hydrofluorocarbons-under-the),
  final rule, 88 FR 73098, October 24, 2023: section on automatic commercial ice machines (self-contained and remote
  definitions, common refrigerants, substitutes and GWPs), used products.
- Code of Federal Regulations, title 40, part 84, as current on November 19, 2026, including earlier versions for
  comparison: [§ 84.52](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-B/section-84.52)
  (definition of install), [§ 84.54](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-B/section-84.54)
  (restrictions, sell-through, what counts as an installation), [§ 84.56](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-B/section-84.56)
  (exemptions), [§ 84.58](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-B/section-84.58)
  (labeling), [§ 84.64](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-B/section-84.64)
  (GWPs), [§ 84.7](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-A/section-84.7)
  (phasedown schedule), [§ 84.106](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-C/section-84.106)
  (leak repair), [§ 84.112](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-C/section-84.112)
  (reclamation).
- U.S. EPA, [Technology Transitions HFC restrictions by sector](https://www.epa.gov/hfcs/technology-transitions-hfc-restrictions-sector)
  (page updated August 28, 2026) and the
  [Technology Transitions fact sheet](https://www.epa.gov/system/files/documents/2026-05/technology-transitions-final-rule-fact-sheet-updated-may-2026.pdf)
  (maintenance of legacy systems, components, sell-through, what counts as a new installation).
- U.S. EPA, [Frequent Questions on the Phasedown of Hydrofluorocarbons](https://www.epa.gov/hfcs/frequent-questions-phasedown-hydrofluorocarbons)
  (page updated November 16, 2026), Technology Transitions: "Is an ice machine a product or a system?", "Can the owner
  of a product … move that equipment …?" and, under Technician Questions, "Can I use existing R-410A components (either
  used or held in inventory) to build a new R-410A system …?".
- U.S. EPA, [Petitions for Reconsideration and Judicial Review Under the AIM Act](https://www.epa.gov/hfcs/petitions-reconsideration-and-judicial-review-under-aim-act)
  (page updated August 13, 2026): NAFEM petition received December 1, 2025, FMI petition received November 7, 2025 and
  NGA petition received December 4, 2025, all "Under Review".
- U.S. EPA, [*Phasedown of Hydrofluorocarbons: Management of Certain Hydrofluorocarbons and Substitutes*](https://www.federalregister.gov/documents/2024/10/11/2024-21967/phasedown-of-hydrofluorocarbons-management-of-certain-hydrofluorocarbons-and-substitutes-under-the),
  final rule, 89 FR 82682, October 11, 2024 (leak repair, reclaimed refrigerant for servicing ice makers, footnote 51 on
  which ice machines are covered, recycling recovered refrigerant in equipment of the same owner).
- FMI – The Food Industry Association, [*Petition for Rulemaking*](https://www.epa.gov/system/files/documents/2026-01/the-food-industry-association-fmi.pdf),
  and National Grocers Association, [petition](https://www.epa.gov/system/files/documents/2026-01/national-grocers-association-nga.pdf):
  both ask the EPA to delete 40 CFR 84.112(e).
- U.S. EPA, [*Listing of Substitutes Under the Significant New Alternatives Policy Program in Commercial and Industrial Refrigeration*](https://www.federalregister.gov/documents/2024/06/13/2024-11690/protection-of-stratospheric-ozone-listing-of-substitutes-under-the-significant-new-alternatives),
  SNAP Rule 26, 89 FR 50410, June 13, 2024, effective July 15, 2024: R-290 in new self-contained commercial ice machines
  (UL 60335-2-89 and the UL 563 transition, markings, no conversion or retrofit, further information on trained
  technicians and RCRA hazardous waste), section II.I.4 on what the venting exemption does not mean, other substitutes,
  GWPs.
- Code of Federal Regulations, title 40, part 82, subpart F (Section 608):
  [§ 82.152](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.152) (small
  appliance), [§ 82.154](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.154)
  (venting prohibition and exempt substitutes),
  [§ 82.161](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.161)
  (technician certification).
- U.S. EPA, [Phaseout of class II ozone-depleting substances](https://www.epa.gov/ods-phaseout/phaseout-class-ii-ozone-depleting-substances)
  (HCFC-22, 2020).
- North American Association of Food Equipment Manufacturers and signatories,
  [*Petition to Extend Transition Period for Automatic Commercial Ice Machines*](https://www.epa.gov/system/files/documents/2026-01/north-american-association-of-food-equipment-manufacturers-nafem.pdf),
  December 1, 2025 (requested dates, low temperature glide, spark-proof components).
- Manitowoc Ice, [*Indigo NXT Air/Water/Remote Condenser Ice Machines Technician's Handbook*](https://www.manitowocice.com/asset/?id=ebxvra),
  Part Number 000018553 Rev 00 04/26: model nomenclature (page 22), R-290 minimum room size and charges (page 29),
  total system refrigerant charge (pages 211–212).
- Hoshizaki America, *Modular Flaker Instruction Manual*, issued 7-27-2017, revised 5-30-2018: F-2001MRJ total
  refrigerant charge with the URC-22F remote condenser (specifications),
  [copy hosted by WebstaurantStore](https://argo.webstaurantstore.com/documents/pdf/415f1002mrjx_manual.pdf).
- U.S. EPA, [ENERGY STAR certified commercial ice machines](https://data.energystar.gov/Active-Specifications/ENERGY-STAR-Certified-Commercial-Ice-Machines/nak5-fsjf)
  (refrigerant by model).

## More guides

- [Ice machine not making ice? Causes, checks and the parts that fix them](https://icepartsdb.com/guides/ice-machine-not-making-ice)
- [Hoshizaki ice machine beeping? What 1, 2, 3, 6 and 7 beeps mean (error codes)](https://icepartsdb.com/guides/hoshizaki-ice-machine-error-codes)
- [Manitowoc ice machine error codes (Indigo NXT E01 to E31): meanings and fixes](https://icepartsdb.com/guides/manitowoc-ice-machine-error-codes)
- [Scotsman ice machine error codes: Prodigy code display meanings and fixes](https://icepartsdb.com/guides/scotsman-ice-machine-error-codes)
- [Ice-O-Matic ice machine error codes: CIM flashing lights, GEM and MFI service lights](https://icepartsdb.com/guides/ice-o-matic-ice-machine-error-codes)
- [How to reset a commercial ice machine (Hoshizaki, Manitowoc, Scotsman, Ice-O-Matic)](https://icepartsdb.com/guides/how-to-reset-commercial-ice-machine)
- [Ice machine water inlet valve: symptoms, testing and replacement](https://icepartsdb.com/guides/ice-machine-water-inlet-valve)
- [Ice machine water pump: symptoms, testing and replacement](https://icepartsdb.com/guides/ice-machine-water-pump)

## Data sources

- [How we build these pages (methodology)](https://icepartsdb.com/legal/editorial-policy)

Last updated: 2026-11-22

Canonical URL: https://icepartsdb.com/guides/ice-machine-refrigerant-r290-epa-rules

Report a correction to this page: https://icepartsdb.com/contact/correction?page=%2Fguides%2Fice-machine-refrigerant-r290-epa-rules