Manitowoc ice machine error codes (Indigo NXT E01 to E31): meanings and fixes
By IcePartsDB · Updated · 8 min read
In this guide · 8 sections
Short answer: Indigo NXT machines show an alert icon on the touchscreen; tap it to open the alert log, where each alert has a short text and an E code. The two that shut the machine down until someone restarts it are E01 Long Freeze (the freeze cycle reached 35 minutes three cycles in a row) and E02 Long Harvest (the harvest reached 7 minutes three cycles in a row). Restart with the green power button or by switching the power off and on, at most three times in 24 hours, and find the cause first. E05 (high pressure cut-out) stops the machine for 10 minutes before it retries; most other codes point to a sensor, the water system or the refrigeration system.
This guide covers the Manitowoc Indigo NXT ice machines (the IYT, IDT, IYF, IDF, IRT and related models, and the R290 models IYP, IDP and IRP), from Manitowoc's Indigo NXT technician's handbook. For any other Manitowoc series, use the technician's handbook for that series.
Safety first. The machine's power switch does not disconnect all incoming power: switch off and lock out the main power supply disconnect before any work inside. R290 (propane) models contain a flammable refrigerant; only refrigeration technicians trained for flammable refrigerants may work on their refrigeration system, and Manitowoc requires their replacement parts to come from its authorized parts network. Other refrigeration work needs a technician certified under EPA Section 608.
How to read alerts on an Indigo NXT
- An alert icon with a number appears on the touchscreen when there are alerts. Tap it to open the alert log, where you can read and clear them. The log is also in the service menu ("Alert Log: lists/clears alerts").
- The data history in the same menu shows minimum and maximum freeze and harvest times, which helps when a fault comes and goes.
- If the machine shuts down on Long Freeze or Long Harvest, a green power button appears on the display.
- Manitowoc advises resetting the control board to factory defaults before troubleshooting, after writing down (or copying to USB) any customer settings, so a changed setting isn't mistaken for a fault.
Every Indigo NXT alert code
| Display text | Code | Meaning | What triggers it |
|---|---|---|---|
| Long Freeze | E01 | Long freeze cycle | The freeze cycle reaches 35 minutes three cycles in a row (each 35-minute freeze is ended by a forced harvest); the machine shuts down |
| Long Harvest | E02 | Long harvest cycle | The harvest reaches 7 minutes three cycles in a row (each one is followed by a thaw cycle); the machine shuts down |
| Power Loss | E03 | Input power loss | Power to the machine was interrupted; logged when it comes back |
| Hi cnd Temp / Wtr Cnd Fault | E04 | High condenser temperature | The liquid line temperature is too high for an air-cooled or water-cooled self-contained machine |
| HPC Fault | E05 | High pressure control opened | The high pressure cut-out switch opened: the machine stops, waits 10 minutes and tries again, repeating while the switch stays open |
| Starving TXV | E07 | Starving expansion valve or low charge (single evaporator) | Evaporator inlet and outlet temperatures differ by more than 12 °F in the last minute of the freeze cycle |
| TXV Fault | E08 | Expansion valve fault (single or dual circuit evaporators) | The same temperature-difference test as E07 |
| Flood Evap1 | E09 | Flooding evaporator, single evaporator, single circuit | The compressor discharge temperature in the first 6 minutes of the freeze cycle doesn't rise far enough above the pre-chill reading |
| Flood Evap2 | E10 | Flooding evaporator, dual expansion valve, dual circuit | The same test as E09 |
| Refrig Fault | E11 | Refrigeration fault | From start-up to 2 minutes into the freeze cycle, the discharge temperature didn't rise by 10 °F and the evaporator temperature didn't fall by 10 °F |
| Curtain Fault | E12 | Curtain switch open more than 24 hours | The machine is set to make ice but has read "bin full" for over 24 hours: curtain open or off |
| Low liq temp | E15 | Fan cycle control fault | The liquid line stays below 60 °F for more than a minute during freeze |
| Rmt Cnd Fault | E16 | Remote condensing unit fault | Remote condensing (CVD) models only: the liquid line goes below 40 °F or above 140 °F for over a minute during freeze |
| ITP Fault | E19 | Ice thickness probe fault | The probe's signal is out of range (unplugged or failed) |
| WTR Fault | E20 | Water system fault | The high water probe senses water but the low one doesn't; or the evaporator outlet is below −10 °F 6.5–7.5 minutes into freeze; or the low water probe still senses water at the end of harvest |
| T1 to T4 Fault | E21 to E24 | Temperature sensor issue | One of the four temperature sensors (thermistors) reads outside its valid range during pre-chill |
| Bin Probe Fault | E25 | Bin level probe low sensor fault | The bin level sensor reads out of range for 10 minutes |
| iAUCS | E28 | Automatic cleaning system | The iAuCS cleaning option was chosen but its board isn't detected; clears when the hardware is detected |
| Safe Mode | E31 | Safe mode | The machine is running on stored cycle data because the water level or ice thickness probe failed |
The parts behind the most common alerts: water level probes (Manitowoc float switches), ice thickness probes and thermistors (Manitowoc thermistors & sensors), Manitowoc water inlet valves, Manitowoc water pumps, Manitowoc condenser fan motors, Manitowoc hot gas valves and Manitowoc control boards.
E01 Long Freeze: what to check
Manitowoc says these shutdowns are most often caused by a minor problem or something outside the machine, often intermittent: a cold room at night, a drop in water pressure, water turned off one night a week. Rule out external and electrical causes before the refrigeration system. Its checklist:
- Installation: work through the installation and visual inspection checklist in the handbook.
- Water: pressure between 20 and 80 psi, inlet water no warmer than 90 °F, a clean water distribution tube, a working water fill valve, dump valve and water pump, no water lost from the sump, and a clean, working water level probe. See the water inlet valve and water pump guides.
- Electrical: low incoming voltage, an ice thickness probe out of adjustment (see the ice thickness probe guide), a harvest that isn't started electrically, a contactor that doesn't energize, a compressor that doesn't run electrically, a failed fan cycling control or fan motor.
- Air and heat: dirty condenser fins or restricted airflow, hot inlet air, or discharge air recirculating to the condenser.
- Refrigeration (technician): non-Manitowoc components, wrong refrigerant charge, non-condensables in the system, restricted high-side lines, a failed head pressure control, harvest valve or compressor, an expansion valve starving or flooding.
E02 Long Harvest: what to check
- Water and scale: a dirty evaporator, a dump valve that doesn't work, the drain vent tube missing, water freezing behind the evaporator, loose plastic extrusions or gaskets on the evaporator, a clogged distribution tube.
- Electrical: an ice thickness probe out of adjustment, or a bin (curtain) switch closed or failed. A harvest can also start too early when the high water probe circuit is made while the low one is open.
- Refrigeration (technician): non-Manitowoc components, wrong refrigerant charge, a failed head pressure control or harvest valve, an expansion valve flooding, a failed fan cycling control, or on water-cooled machines a water regulating valve adjusted wrongly or not closing during harvest.
Thaw cycle and safe mode
Two sequences keep an Indigo NXT making ice while an alert is active:
- Thaw cycle: if the curtain doesn't open within the 7-minute harvest, the machine stops the refrigeration and circulates, dumps and refills water 18 times to melt the ice off (1 to 1¾ hours, depending on the model), then starts a new freeze. To end it early, turn the machine off and on with the keypad; cutting the power instead restarts it in a harvest cycle.
- Safe mode (E31): if the ice thickness probe (E19) or the water level probe (E20) fails, the board runs the machine on its model data and recent cycle history for up to 72 hours, then goes to standby and turns off. It leaves safe mode by itself if the sensor starts working again.
Restarting after a shutdown
After a Long Freeze or Long Harvest shutdown, press the green power button on the display, or switch the power off and on. The board allows this only three times in 24 hours. Find the cause first: the same fault will stop the machine again.
Questions and answers
What does E01 mean on a Manitowoc ice machine?
E01 is Long Freeze: the freeze cycle reached 35 minutes in three cycles in a row, and the machine shut down. Manitowoc says these shutdowns are most often caused by something outside the machine, such as low water pressure, warm water or a cold room at night; its checklist also includes a dirty water level probe, a clogged distribution tube and a dirty condenser. Refrigeration faults come last.
What does E02 mean on a Manitowoc ice machine?
E02 is Long Harvest: the harvest reached 7 minutes in three cycles in a row, and the machine shut down (each long harvest is followed by a thaw cycle). Manitowoc's checklist includes a dirty evaporator, a stuck curtain or bin switch, the ice thickness probe adjustment, the dump valve and the harvest valve.
How do I reset a Manitowoc Indigo NXT ice machine?
Press the green power button that appears on the display after a Long Freeze or Long Harvest shutdown, or switch the power off and on. It can be restarted this way three times in 24 hours. Clear old alerts in the alert log. Other brands: how to reset a commercial ice machine.
What is Curtain Fault (E12) on a Manitowoc?
The machine has been set to make ice but has read "bin full" for more than 24 hours: the water curtain is open, off, or its switch isn't working. The bin switch is a magnetic reed switch, so refit the curtain and check that its magnet is in place.
What is Safe Mode on a Manitowoc ice machine?
When the ice thickness probe or the water level probe fails, the machine keeps making ice on stored cycle data for up to 72 hours, then turns off. Replace the failed probe within that time.
Sources
- Manitowoc Ice, Indigo NXT Air/Water/Remote Condenser Ice Machines Technician's Handbook, Part Number 000018553 Rev 00 04/26: safety notices (pages 8–9), restart rules (page 62), alert log and alert log detail (pages 85–91), E01 and E02 checklists (pages 92–95), reset to factory defaults (page 97), bin switch (page 150), high pressure cut-out (page 174).
- Handbooks for other series are on manitowocice.com under each model's documents.
Browse by brand
More guides
- Ice machine not making ice? Causes, checks and the parts that fix them
- Hoshizaki ice machine beeping? What 1, 2, 3, 6 and 7 beeps mean (error codes)
- Scotsman ice machine error codes: Prodigy code display meanings and fixes
- Ice-O-Matic ice machine error codes: CIM flashing lights, GEM and MFI service lights
- How to reset a commercial ice machine (Hoshizaki, Manitowoc, Scotsman, Ice-O-Matic)
- Ice machine water inlet valve: symptoms, testing and replacement
- Ice machine water pump: symptoms, testing and replacement
- Ice machine float switch and water level probe: symptoms, testing and replacement
- Ice machine control board: signs of failure, what to check first, and replacement
- Ice thickness probe and thermistor: how ice machines decide when to harvest
- Ice machine condenser fan motor: symptoms, testing and replacement
- Ice machine bin control: bin thermostats, curtain switches and ice level sensors
- Flake and nugget ice machine auger and gear motor: wear, noise and replacement
- How to clean and sanitize a commercial ice machine (and how often)
- How to find your ice machine's model number and the right part number
- Ice machine serial number lookup: how old is my Hoshizaki, Manitowoc, Scotsman or Ice-O-Matic?
- How long do commercial ice machines last? Lifespan, what shortens it and when to replace
- Ice machine recalls: is your ice machine affected?
- What size ice machine do I need? How to size a commercial ice machine
- Cube vs nugget vs flake ice: the ice types and the machines that make them
- Air-, water- or remote-cooled ice machine? Running costs compared
- How much does a commercial ice machine cost? Machines, running costs, repairs and parts
- Ice machine water filters: why they matter, when to change them and how to size one
- Buying a used commercial ice machine on eBay: a checklist
- OEM vs aftermarket ice machine parts: price gap and when each makes sense
- Hoshizaki vs Manitowoc vs Scotsman: which commercial ice machine brand is best?
- Ice machine refrigerants and the EPA rules: R-404A, R-410A, R-134a, R-290 and the 2026–2027 deadlines
Data sources
- IcePartsDB editorial — written from the data above, the sources linked in the text and general trade practice; not a substitute for the machine's manual or a qualified technician
- How we build these pages (methodology)
- Report a correction to this page
Last updated